  • Conductivity Sensor SC210G

Conductivity Sensor SC210G

2016-05-27 14:51:12

Description:

Yokogawa has been supplying superior on-line analyzers for monitoring or controlling the conductivity of liquids or solutions. Now, Yokogawa provides the SC450G four-wire conductivity/resistivity converter, the SC202G and SC202S two-wire conductivity/resistivity transmitters, and the SC100 panel mount conductivity converter. Yokogawa also provides many kinds of sensors for accurately measuring liquid conductivity when using converters/transmitters. The combination of Yokogawa's converters/transmitters and sensors meets the demanding ultrapurewater requirements of the growing semiconductor and pharmacentical markets in addition to the traditional water quality measurement requirements of standard power plant and chemical applications. The SC210G conductivity sensor is widely used in various water and manufacturing process applications. A wide variety of mountings are available including screw-in type, flange type, flow-through type, and screw-in type with gate valve.……

New Products

Siemens 6ES7215-1AF40-0XB0 CPU 1215 FC SIMATIC S7-1200F

Siemens 6ES7215-1AF40-0XB0 CPU 1215 FC SIMATIC S7-1200F available at HKXYTECH. Get in touch today for a quick price.

Emerson TREXLFPKLWS3S AMS Trex device communicator

Emerson TREXLFPKLWS3S AMS Trex device communicator. HART and FOUNDATION fieldbus applications, ATEX, CSA US/Canada and IECEx intrinsically safe, Wireless, Standard support 3 year, Carrying Case

Emerson TREXLHPKLWS1S AMS Trex device communicator

Emerson TREXLHPKLWS1S AMS Trex device communicator. HART Application, ATEX, CSA US/Canada and IECEx intrinsically safe, Wireless, Standard support 1 year, Carrying Case.

ABB CI854BK01 3BSE069449R1 PROFIBUS-DP/V1 interface

Package including: CI854 Communication Interface and TP854 Baseplate

Assortments

Description

Conductivity Sensor SC210G

Yokogawa has been supplying superior on-line analyzers for monitoring or controlling the conductivity of liquids or solutions.

Now, Yokogawa provides the SC450G four-wire conductivity/resistivity converter, the SC202G and SC202S two-wire conductivity/resistivity transmitters, and the SC100 panel mount conductivity converter. Yokogawa also provides many kinds of sensors for accurately measuring liquid conductivity when using converters/transmitters.

The combination of Yokogawa's converters/transmitters and sensors meets the demanding ultrapurewater requirements of the growing semiconductor and pharmacentical markets in addition to the traditional water quality measurement requirements of standard power plant and chemical applications.

The SC210G conductivity sensor is widely used in various water and manufacturing process applications. A wide variety of mountings are available including screw-in type, flange type, flow-through type, and screw-in type with gate valve.

Specifications

Object of measurementConductivity of liquids or solutions
Measuring principleTwo-electrode system
Cell constant0.05 cm-1, 5 cm-1
Measuring range0-0.5 to 0-200 μS/cm (Cell constant: 0.05 cm-1)
0-200 μS/cm to 0-20 mS/cm (Cell constant: 5 cm-1)
Temperature Range0 to 105 deg C (chamber material: SCS14)
0 to 100 deg C (chamber material: Polypropylene)
Pressure range0 to 1 MPa (chamber material: SCS14)
0 to 500 kPa(chamber material: Polypropylene)
Measuring solution conditionFlow rate: less than 20 l/min is recommended for flow-through type.
Air bubbles should not be mixed in the sample solutions to obtain correct measured values.
Temperature sensorPB36 NTC
ConstructionJIS C0920 watertight (equivalent to NEMA4)
Process connectionScrew-in, Flange, Flow-through, with gate valve