Watson Smith Fail freeze I/P Converter Type 422 AC0111
2016-04-13 15:48:44
Description:
Watson Smith Fail freeze I/P Converter Type 422 AC0111; The Watson Smith current to pressure converter (I/P converter) Type 422 with its Fail freeze (fail in last position) feature is ideal for field applications. This unit is available with Intrinsically Safe certification.……
Notice:
Watson Smith Fail freeze I/P Converter Type 422 AC0111, brand new, original in UK;
New Products
Allen-Bradley 25B-V4P8N104 PowerFlex 525 low voltage AC drives - Rockwell
Allen-Bradley 25B-V4P8N104 PowerFlex 525 AC Drive, with Embedded EtherNet/IP and Safety, 120 VAC, 1 Phase, 4.8 Amps, 1.0 HP, 0.75 kW Normal Duty; 1.0 HP, 0.75 kW Heavy Duty, Frame B, IP20 NEMA / Open Type, No Filter.
Allen-Bradley 25B-V6P0N104 PowerFlex 525 low voltage AC drives - Rockwell
Allen-Bradley 25B-V6P0N104 PowerFlex 525 AC Drive, with Embedded EtherNet/IP and Safety, 120 VAC, 1 Phase, 6 Amps, 1.5 HP, 1.1 kW Normal Duty; 1.5 HP, 1.1 kW Heavy Duty, Frame B, IP20 NEMA / Open Type, No Filter.
Allen-Bradley 25B-D4P0N114 PowerFlex 525 low voltage AC drives - Rockwell
Allen-Bradley 25B-D4P0N114 PowerFlex 525 AC Drive, with Embedded EtherNet/IP and Safety, 480 VAC, 3 Phase, 4 Amps, 2 HP, 1.5 kW Normal Duty; 2 HP, 1.5 kW Heavy Duty, Frame A, IP20 NEMA / Open Type, Filter.
Allen-Bradley 25B-D6P0N104 PowerFlex 525 low voltage AC drives - Rockwell
Allen-Bradley 25B-D6P0N104 PowerFlex 525 AC Drive, with Embedded EtherNet/IP and Safety, 480 VAC, 3 Phase, 6 Amps, 3 HP, 2.2 kW Normal Duty; 3 HP, 2.2 kW Heavy Duty, Frame A, IP20 NEMA / Open Type, No Filter.
Assortments
Description
Watson Smith Fail freeze I/P Converter Type 422 AC0111
The Watson Smith current to pressure converter (I/P converter) Type 422 with its Failfreeze (fail in last position) feature is ideal for field applications. This unit is available with Intrinsically Safe certification.
ATEX I.S. I/P Converter Advanced electronic control Fail freeze operation (output pressure retained on power failure) Minimum vibration effects High accuracy Captured bleed as standard;
All electronic I/P converters have closed loop control, excellent vibration resistance, long term stability and can be mounted in any orientation.
4-20mA signal and a range of output variations.
Electronic I/P Converters Type 422 (Watson Smith Failfreeze I/P Converter Type 422)
All electronic I/P converters have closed loop control, excellent vibration resistance, long term stability and can be mounted in any orientation. 4-20mA signal and a range of output variations.
Specifications:
3-15psi, 3-120psi, 0.2-1bar, 0.2-8bar output options
High Flow - 280 l/min (10scfm)
Faifreeze drift rate < 2% setpoint/hour
IP65 rating
Type N or Intrinsically Safe options
Technical features Medium: Oil free, dry air, filtered to 5 μm Output pressure: 0,2 ... 1 bar
Supply pressure: at least 0,7 bar above maximum required output pressure maximum 4 bar gauge
Flow capacity: Up to 250 Nl/min Air consumption: √ 0,4 Nl/min
Linearity: 0,5 % of span
Hysteresis: Typically 0,5% of span
Vibration effect: 1 % of span for vibration level up to 4 mm, 5 ... 15 Hz, 3g 15 ... 500 Hz in any orientation.
Response time: < 6 sec 10 ... 90% into a 0,5 l volume < 6 sec 90 ... 10% into a 0,5 l volume
Temperature sensitivity: Typically < 0,1 % span/°C between -10°C and +60°
Supply sensitivity: Typically < 0,5% of span for full supply pressure range
Port sizes: Main ports: 1/4 NPT/G1/4 female Gauge ports: 1/4 NPT/G1/4 female Captured bleed: 1/8 NPT female I.P.
Rating:
IP65 with piped exhaust
EMC Compatibility: Compliant and CE marked in accordance with the EC Directive 2004/108/EC tested to BS EN 61000-6-2:2005 BS EN 61000-6-4:2007+ A11:2011 Ambient/Media temperature: -10 ... +70°C Air supply must be dry enough to avoid ice formation at temperatures below +2°C.
Maintenance No user serviable parts
Mounting position: Operation in any orientation is possible;
integral surface mounting bracket provided. Orientation effect <0.2%
Materials
Body: zinc diecasting
passivated and epoxy painted
Cover: Glass reinforced PA
Diaphragms: NBR;
Electrical parameters:
Input Signal :4 ... 20 mA (two wire). Terminal voltage typically < 11 V at 20 mA
Failure Mode Output pressure held at previous value when input signal fails; drift rate 0,2% of span in 5 minutes
Overload protection 30 mA max. overload current. Unit unaffected by reverse current
Connections 30mm square connector provided (DIN 43650, form A) mountable in 4 directions
Span/Zero Independently adjustable up to 15 % output range;
We keep the standard model AC0100 (4-20mA input / 3-15 psi output) in stock.
List of available models (all of the following are suitable replacement units for model starting with "53"):
AC0100, AC0101, AC0111, AC012X, AC037X, AC039X, AC134X, AC138X, AC2100;