Yokogawa RTD Input Module AAR181-S53-hkxytech
  • Yokogawa RTD Input Module AAR181-S53

Yokogawa RTD Input Module AAR181-S53

2016-03-22 20:56:47

Description:

Yokogawa RTD Input Module AAR181-S53,Yokogawa Analog I/O modules function as signal converters; by inputting field analog signals into these modules . AAR181A, AAT141 These modules receive signals from mV, thermocouple (TC), and RTD. They can be used in dual-redundant ……

Notice:
Yokogawa RTD Input Module AAR181-S53,Yokogawa original packing, by carton,Place of Origin: Indonesia

New Products

Emerson TREXCHPNAWS3S AMS Trex device communicator

Emerson TREXCHPNAWS3S AMS Trex device communicator, HART Application, Wireless Capability, 3 Years Standard Support, Carrying Case. Enables HART or Fieldbus Module device communications, 5.7 inch touchscreen display, intrinsically safe.

Emerson TREXCHPNAWS3 AMS Trex device communicator

Emerson TREXCHPNAWS3 AMS Trex device communicator, HART Application, Wireless Capability, 3 Years Standard Support. Enables HART or Fieldbus Module device communications, 5.7 inch touchscreen display, intrinsically safe.

Emerson TREXCHPNAWS1S AMS Trex device communicator

Emerson TREXCHPNAWS1S AMS Trex device communicator, HART Application, Wireless Capability, 1 Year Standard Support, Carrying Case. Enables HART or Fieldbus Module device communications, 5.7 inch touchscreen display, intrinsically safe.

Emerson TREXCHPNAWS1 AMS Trex device communicator

Emerson TREXCHPNAWS1 AMS Trex device communicator, HART Application, Wireless Capability, 1 Year Standard Support. Enables HART or Fieldbus Module device communications, 5.7 inch touchscreen display, intrinsically safe.

Assortments

Description

Yokogawa RTD Input Module AAR181-S53 

  

   STANDARD SPECIFICATIONS of  AAR181-S53

      TC/RTD Input Modules (Isolated) 

     AAR181A, AAT141 These modules receive signals from mV, thermocouple (TC), and RTD. They can be used in dual-redundant 

      

     

ItemsSpecifications
ModelAAT141AAR181
Number of input channels16, isolated (*7)12, isolated
Input signalTC: JIS C1602:1995, IEC584:1995
Type J, K, E, B(*1), R, S, T, N
mV: -100 to 150 mV, -20 to 80 mV
RTD: JIS C1604:1997, IEC751:1995
Pt100 (3-wire type)(*6)
Switching input signalsTC/mV can be set individually for CH1 to CH16.CH1 to CH12 are RTD inputs.
Allowable input voltage±5 V±5 V
Withstanding voltageBetween input and system: 1500 V AC, for 1 minute
Input resistancePower ON 2 MΩ or larger
Power OFF 2 MΩ or larger
AccuracyTC: ±30 μV
MV: ±80 μV for span (-100 to 150 mV)
±30 μV for span (-20 to 80 mV)
RTD: ±120 mΩ
Allowable total resistance of
signal source plus wiring
1000 Ω or less40 Ω or less (wiring resistance per wire) (*2)
Effect of allowable signal source
resistance (1000 Ω)
±20 μV(*3)
Reference junction compensation
accuracy
Within ±1 °C (*4) (*5)
Measurement current
RTD: 1 mA
Temperature drift±80 μV/10 °C (-100 to 150 mV input)
±30 μV/10 °C (TC/-20 to 80 mV input
±120 mΩ/10 °C (RTD input)
Data update period1 s
Burn-outAll channels can be set together.
Setting: Not available/available (UP/DOWN)
Detection time: 60 s

Maximum current consumption450 mA (5 V DC)450 mA (5 V DC)
Weight0.2 kg

 

Yokogawa RTD Input Module AAR181-S53  

 

  

   EXTERNAL DIMENSIONS of  AAR181-S53

 

 

     Yokogawa RTD Input Module AAR181-S53   

MODEL AND SUFFIX CODES  AAR181-S53



Description
ModelAAR181RTD Input Module (12-channel, Isolated)

-SStandard type
Suffix
Codes
   5With no explosion protection

   EWith explosion protection

      0Basic type

      3With ISA Standard G3 option and temperature (-20 to 70 °C) option
Option
Codes



/R8S00With Pressure Clamp Terminal Block for RTD [Model: ATR8S-00]

/R8S10With Pressure Clamp Terminal Block for RTD (surge absorber) [Model: ATR8S-10]

/R8D00With Dual Pressure Clamp Terminal Block for RTD [Model: ATR8D-00]

/R8D10With Dual Pressure Clamp Terminal Block for RTD (surge absorber) [Model: ATR8D-10]

/CCC01With Connector Cover for MIL Cable [Model: ACCC01

 

 

 

Yokogawa RTD Input Module AAR181-S53