Yokogawa Analog Output Module AAI543-H00
2016-03-22 20:19:45
Description:
Yokogawa Analog Output Module AAI543-H00, Yokogawa Analog I/O modules function as signal converters; by inputting field analog signals into these modules ……
Yokogawa Analog Output Module AAI543-H00, Place of Origin: Indonesia, Yokogawa original packing, by carton
New Products
Siemens 6DL1193-6TP00-0DH1 SIMATIC ET 200SP HA
Siemens 6DL1193-6TP00-0DH1 SIMATIC ET 200SP HA, Terminal block, Type H1, 32 push-in terminals, internal reference temperature New load group, width: 22.5 mm.
Siemens 6DL1193-6TP00-0BH1 SIMATIC ET 200SP HA
Siemens 6DL1193-6TP00-0BH1 SIMATIC ET 200SP HA, Terminal block, Type H1, 32 push-in terminals, internal reference temperature Width: 22.5 mm.
Siemens 6DL1193-6GC00-0NN0 SIMATIC ET 200SP HA
Siemens 6DL1193-6GC00-0NN0 SIMATIC ET 200SP HA, carrier module 8-fold carrier for holding 8 I/O modules of the ET 200SP HA.
Siemens 6DL1193-6GA00-0NN0 SIMATIC ET 200SP HA
Siemens 6DL1193-6GA00-0NN0 SIMATIC ET 200SP HA, carrier module 2-fold carrier for holding 2 I/O modules of the ET 200SP HA.
Assortments
▶ Pressure Transmitter EJA
▶ Pressure Transmitters EJA-E
▶ Pressue Transmitter EJX
▶ Safety Instrumented System (SIS)
▶ Valve Positioners & Converters
▶ Field Mount Indicators
▶ Temperature Transmitters
▶ Magnetic Flowmeters
▶ Vortex Flowmeter
▶ Ultrasonic Flowmeters
▶ Coriolis Mass Flowmeters - ROTAMASS 3-Series
▶ Variable Area Flowmeters – Rotameters
▶ Device Smart Communicators
▶ PORTABLE AND HANDHELD INSTRUMENTS
▶ Distributed Control System (DCS)
▶ Process Analyzers
▶ Paperless Recorders
▶ Strip Chart Recorders
▶ Data Acquisition Equipment
▶ UT Series Temperature Controllers
▶ UP Series Program Controllers
▶ UM Series Digital Indicators with Alarms
▶ UT100 Series Temperature Controllers
▶ UD Series Manual Setters
▶ Limit Controllers
▶ YS Series Single-loop Controllers
Description
Yokogawa Analog Output Module AAI543-H00
STANDARD SPECIFICATIONS of AAI543-H00
Current/Voltage Input Modules (Non-Isolated)
These modules provide 16 inputs of mainly 4 to 20 mA DC or 1 to 5 V DC standardized signals from 2-wire/4-wire transmitters.
They can be used in dual-redundant configuration.
Current Output Module (Isolated)
AAI543 provides 16 outputs of 4 – 20 mA signal. It can be used in dual-redundant configuration. (*1)
Items | Specifications |
Model | AAI543 |
Number of output channels | 16, isolated, standard switch-over response in redundant configuration (*3) |
Output signal | 4 to 20 mA |
Withstanding voltage | Between output and system: 1500 V AC, for 1 minute (4) |
Allowable load resistance | 0 to 750 Ω |
Circuit-open detection | Less than 0.65 mA |
Accuracy | ±48 μA |
Data update period | 10 ms |
Drift due to ambient temperature change | ±16 μA/10 C |
Maximum current consumption | 230 mA (5 V DC), 540 mA (24 V DC) |
Weight | 0.4 kg |
External communication | Pressure clamp terminal, MIL connector cable, dedicated cable (KS1) |
HART communication (5) | Available |
*1: A dual-redundant configuration is enabled by using two identical modules with the same suffix codes.
*2: When AAI543 is installed in a ER bus node unit, use it in the ambient temperature within 0 to 60 ºC range.
*3: When a switch over from control to stand-by module takes place in the dual-redundant configuration, the maximum period
of time when the field output falls below 4 mA is 100 ms for AAI543-0 (standard switch-over response) and 2 ms for
AAI543-1(fast switch-over response). In case of connecting fast response type field devices, use AAI543-1 (fast
switch-over response) in the dual-redundant configuration.
*4: When the dedicated cable is used, the withstanding voltage is 500 V AC (between the input signal and the system). When
the ML connector cable is used, the withstanding voltage depends on the electrical specifications of the cable.
*5: When this module is installed in a ER bus node unit with HART function, the EB401 firmware must be rev. 2 or later.
Yokogawa Analog Output Module AAI543-H00
EXTERNAL DIMENSIONS of AAI543-H00
Yokogawa Analog Output Module AAI543-H00
MODEL AND SUFFIX CODES AAI543-H00
Description | ||
Model | AAI543 | Analog Output Module (4 to 20 mA 16-channel Isolated) |
-S | Standard Type | |
-H | With digital communication (HART protocol) | |
Suffix Codes | 5 | Standard switch-over response in redundant configuration with no explosion protection(*1) |
6 | Fast switch-over response in redundant configuration with no explosion protection(*2) | |
E | Standard switch-over response in redundant configuration with explosion protection(*1) | |
F | Fast switch-over response in redundant configuration with explosion protection(*2) | |
0 | Basic type | |
1 | With ISA Standard G3 option | |
3 | With ISA Standard G3 option and temperature (-20 to 70 C) option | |
Option Codes | /K4A00 | With KS Cable Interface Adapter [Model ATK4A-00] |
/A4S00 | With Pressure Clamp Terminal Block for Analog [Model ATA4S-00] | |
/A4S10 | With Pressure Clamp Terminal Block for Analog (surge absorber) [Model ATA4S-10] | |
/A4D00 | With Dual Pressure Clamp Terminal Block for Analog [Model ATA4D-00] | |
/A4D10 | With Dual Pressure Clamp Terminal Block for Analog (surge absorber) [Model ATA4D-10] | |
/CCC01 | With Connector Cover for MIL Cable [Model ACCC01] |
*1: If “standard switch-over response in redundant configuration” is selected, “basic type” or “with ISA Standard G3 option and
temperature (-20 to 70 °C) option” may be specified.
*2: If “fast switch-over response in redundant configuration” is selected, “basic type” or “with ISA Standard G3 option” may be
specified.
Yokogawa Analog Output Module AAI543-H00