Top Industrial Automation and Electrical Instrument from HKXYTECH
  • Yokogawa Analog Output Module AAI543-H00

Yokogawa Analog Output Module AAI543-H00

2016-03-22 20:19:45

Description:

Yokogawa Analog Output Module AAI543-H00, Yokogawa Analog I/O modules function as signal converters; by inputting field analog signals into these modules ……

Yokogawa Analog Output Module AAI543-H00, Place of Origin: Indonesia, Yokogawa original packing, by carton

New Products

Siemens 6DL1193-6TP00-0DH1 SIMATIC ET 200SP HA

Siemens 6DL1193-6TP00-0DH1 SIMATIC ET 200SP HA, Terminal block, Type H1, 32 push-in terminals, internal reference temperature New load group, width: 22.5 mm.

Siemens 6DL1193-6TP00-0BH1 SIMATIC ET 200SP HA

Siemens 6DL1193-6TP00-0BH1 SIMATIC ET 200SP HA, Terminal block, Type H1, 32 push-in terminals, internal reference temperature Width: 22.5 mm.

Siemens 6DL1193-6GC00-0NN0 SIMATIC ET 200SP HA

Siemens 6DL1193-6GC00-0NN0 SIMATIC ET 200SP HA, carrier module 8-fold carrier for holding 8 I/O modules of the ET 200SP HA.

Siemens 6DL1193-6GA00-0NN0 SIMATIC ET 200SP HA

Siemens 6DL1193-6GA00-0NN0 SIMATIC ET 200SP HA, carrier module 2-fold carrier for holding 2 I/O modules of the ET 200SP HA.

Assortments

Description

Yokogawa Analog Output Module AAI543-H00  

  

   STANDARD SPECIFICATIONS of AAI543-H00  

   Current/Voltage Input Modules (Non-Isolated)
   These modules provide 16 inputs of mainly 4 to 20 mA DC or 1 to 5 V DC standardized signals from 2-wire/4-wire transmitters.
  They can be used in dual-redundant configuration.

    

     

      Current Output Module (Isolated)      

     AAI543  provides 16 outputs of 4 – 20 mA signal. It can be used in dual-redundant configuration. (*1)  

 

ItemsSpecifications
ModelAAI543
Number of output channels16, isolated, standard switch-over
response in redundant configuration (*3)
Output signal4 to 20 mA
Withstanding voltageBetween output and system: 1500 V AC, for 1 minute (4)
Allowable load resistance0 to 750 Ω
Circuit-open detectionLess than 0.65 mA
Accuracy±48 μA
Data update period10 ms
Drift due to ambient temperature change±16 μA/10 C
Maximum current consumption230 mA (5 V DC), 540 mA (24 V DC)
Weight0.4 kg
External communicationPressure clamp terminal, MIL connector cable, dedicated cable (KS1)
HART communication (5)Available

  *1: A dual-redundant configuration is enabled by using two identical modules with the same suffix codes.
*2: When AAI543 is installed in a ER bus node unit, use it in the ambient temperature within 0 to 60 ºC range.
*3: When a switch over from control to stand-by module takes place in the dual-redundant configuration, the maximum period
of time when the field output falls below 4 mA is 100 ms for AAI543-0 (standard switch-over response) and 2 ms for
AAI543-1(fast switch-over response). In case of connecting fast response type field devices, use AAI543-1 (fast
switch-over response) in the dual-redundant configuration.
*4: When the dedicated cable is used, the withstanding voltage is 500 V AC (between the input signal and the system). When
the ML connector cable is used, the withstanding voltage depends on the electrical specifications of the cable.
*5: When this module is installed in a ER bus node unit with HART function, the EB401 firmware must be rev. 2 or later.

 

 

 Yokogawa Analog Output Module AAI543-H00   

 

EXTERNAL DIMENSIONS of AAI543-H00 

 

 

 Yokogawa Analog Output Module AAI543-H00   

MODEL AND SUFFIX CODES AAI543-H00



Description
ModelAAI543   Analog Output Module (4 to 20 mA 16-channel Isolated)

-SStandard Type

-HWith digital communication (HART protocol)
Suffix
Codes
   5Standard switch-over response in redundant configuration with no explosion protection(*1)

   6Fast switch-over response in redundant configuration with no explosion protection(*2)

   EStandard switch-over response in redundant configuration with explosion protection(*1)

   FFast switch-over response in redundant configuration with explosion protection(*2)

      0Basic type

      1With ISA Standard G3 option

      3With ISA Standard G3 option and temperature (-20 to 70 C) option
Option
Codes
/K4A00With KS Cable Interface Adapter [Model ATK4A-00]

/A4S00With Pressure Clamp Terminal Block for Analog [Model  ATA4S-00]

/A4S10With Pressure Clamp Terminal Block for Analog (surge absorber) [Model ATA4S-10]

/A4D00With Dual Pressure Clamp Terminal Block for Analog [Model ATA4D-00]

/A4D10With Dual Pressure Clamp Terminal Block for Analog (surge absorber) [Model ATA4D-10]

/CCC01With Connector Cover for MIL Cable [Model ACCC01]

 

  *1: If “standard switch-over response in redundant configuration” is selected, “basic type” or “with ISA Standard G3 option and
temperature (-20 to 70 °C) option” may be specified.
*2: If “fast switch-over response in redundant configuration” is selected, “basic type” or “with ISA Standard G3 option” may be
specified.

 

 

 

 Yokogawa Analog Output Module AAI543-H00