Top Industrial Automation and Electrical Instrument from HKXYTECH
  • yokogawa EJA530A-EBS4N-04DN eja530 eja530a EJA530 EJA530A
  • yokogawa EJA530A-EBS4N-04DN eja530 eja530a EJA530 EJA530A
  • yokogawa EJA530A-EBS4N-04DN eja530 eja530a EJA530 EJA530A

yokogawa EJA530A-EBS4N-04DN eja530 eja530a EJA530 EJA530A

2015-06-16 15:49:09

Description:

The gauge pressure transmitter model EJA530A/HAC can be used to measure liquid, gas, or steam pressure. Both output a 4 to 20 mA DC signal corresponding to the measured pressure, and also feature remote setup and monitoring through communications with the BRAIN™ terminal and CENTUM CS™ or μXL™ or HART® 275 host.……

New Products

Siemens 6DL1193-6TP00-0DH1 SIMATIC ET 200SP HA

Siemens 6DL1193-6TP00-0DH1 SIMATIC ET 200SP HA, Terminal block, Type H1, 32 push-in terminals, internal reference temperature New load group, width: 22.5 mm.

Siemens 6DL1193-6TP00-0BH1 SIMATIC ET 200SP HA

Siemens 6DL1193-6TP00-0BH1 SIMATIC ET 200SP HA, Terminal block, Type H1, 32 push-in terminals, internal reference temperature Width: 22.5 mm.

Siemens 6DL1193-6GC00-0NN0 SIMATIC ET 200SP HA

Siemens 6DL1193-6GC00-0NN0 SIMATIC ET 200SP HA, carrier module 8-fold carrier for holding 8 I/O modules of the ET 200SP HA.

Siemens 6DL1193-6GA00-0NN0 SIMATIC ET 200SP HA

Siemens 6DL1193-6GA00-0NN0 SIMATIC ET 200SP HA, carrier module 2-fold carrier for holding 2 I/O modules of the ET 200SP HA.

Assortments

Description

Quick Details

  • Place of Origin: Japan

  • Brand Name: Yokogawa

  • Model Number: EJA530A-DAS4N-02DE

  • Up-scale: 110%, 21.6 mA DC or more

  • Down-scale: -5%, 3.2 mA DC or less

  • Altitude of installation site:: Max. 2,000 m above sea level

  • Load Capacitance: 0.22 uF or less

  • Load Inductance: 3.3 mH or less

  • Spacing from power line: 15 cm or more.

  • Degrees of Protection: IP67, NEMA4X

  • Cover O-rings: Buna-N, fluoro-rubber (optional)

  • Data plate and tag: SUS304 or SUS316 (option)

  • Fill Fluid: Silicone, Fluorinated oil (option)


Packaging & Delivery

Packaging Details:NEW FACTORY SEAL / ALL EJA530A EJA510A ORIGINAL PACKING
Delivery Detail:1-2 weeks after received order's payment


Why do you choose us?

1. 100% original package product, 100% quality assurance

If you find a fake product. Please contact us without hesitation! We afford the shipment cost! We send you a new product asking zero cent!

 2. Varied payment methods.

 We adopt L/C, D/A, D/P, T/T, and other methods. If you can not trust us , you can choose to pay it via Ali-express100% make your money safe!


EJA510A Absolute and Gauge Pressure Transmitter EJA530A

 

 

 

 

 

Features:

Excellent performance and stability

The EJA series uses a silicon resonant sensor formed from monocrystal silicon, a perfect material which has no hysteresis in pressure or temperature changes. The sensor minimizes overpressure, temperature change, and static pressure effects, and thus offers unmatched long-term stability.

Compact and light-weight design

Half the weight of conventional models thanks to miniaturization of the casing with the amplifier ASIC, pressure cell structure, and flange. The ASIC uses the minimum number of parts and improves the reliability of the amplifier.

Fieldbus communication capability

Fieldbus is a digital two-way communication system. It is a revolutionary technology for configuring instrumentation control systems and a promising successor to the standard 4 to 20 mA analog communication used in most field instruments today.
EJA series offers two types of fieldbus models, FOUNDATION™ fieldbus Low Voltage Mode and PROFIBUS PA devices, which ensure interoperability between Yokogawa and other manufactures. As for software, the EJA series incorporates two AI function blocks that compute differential and static pressures to allow flexible configuration of instrumentation.

 

Specifications:

 

 


EJA510A / EJA530A Direct Mount Type Absolute Pressure and Gauge Pressure Transmitter
(Measurement values below are in absolute for EJA510A)

A Capsule

B Capsule

C Capsule

D Capsule

Range

0 to 200 kPa
(0 to 29 psi)

0 to 2 MPa
(0 to 290 psi)

0 to 10 MPa
(0 to 1450 psi)

0 to 50 MPa
(0 to 7200 psi)

Span

10 to 200 kPa
(1.45 to 29 psi)

0.1 to 2 MPa
(14.5 to 290 psi)

0.5 to 10 MPa
(72.5 to 1450 psi)

5 to 50 MPa
(720 to 7200 psi)

Accuracy

±0.2%

±0.2%

±0.2%

±0.2%

Degrees of protection

IP67, NEMA 4X, and JIS C0920 immersion proof

Certificates

FM, CENELEC ATEX, CSA, IECEx

Output

4 to 20 mA DC or FOUNDATION™ fieldbus or PROFIBUS PA 2-wire system with digital communication

Supply voltage

BRAIN and HART:10.5 to 42 V DC (10.5 to 30 V DC for Intrinsically safe type)
Fieldbus:9 to 32 V DC (9 to 24 V DC for Entity model and 9 to 17.5 V DC for FISCO model)

Ambient temperature

-40 to 85 deg C (-40 to 185 deg F) (general use type)
-30 to 80 deg C (-22 to 176 deg F) (with integral indicator)

Process temperature

-40 to 120 deg C (-40 to 248 deg F) (general use type)

Maximum overpressure

4 MPa
(580 psi)

4 MPa
(580 psi)

20 MPa
(2900 psi)

60 MPa
(8500 psi)

Mounting

Direct Mounting/2-inch pipe mounting

Wetted parts material

Capsule

Hastelloy C-276

Process
connection

SUS316L, Hastelloy C-276

Housing

Cast aluminum


 

 

Ordering Examples:

 

 

 

 

EJA530A-DAS4N-02DE

 

EJA530A-DBS4N-04DN

 

EJA530A-DCS4N-07DF

 

EJA530A-DDS4N-09DN