Top Industrial Automation and Electrical Instrument from HKXYTECH
  • Yokogawa Analog Input Module AAV144-SE3

Yokogawa Analog Input Module AAV144-SE3

2016-03-22 17:15:14

Description:

Yokogawa Analog Input Module AAV144-SE3,Yokogawa Analog I/O modules function as signal converters; by inputting field analog signals into these modules ……

Yokogawa Analog Input Module AAV144-SE3,Place of Origin: Indonesia,Yokogawa original packing, by carton

New Products

Siemens 6DL1193-6TP00-0DH1 SIMATIC ET 200SP HA

Siemens 6DL1193-6TP00-0DH1 SIMATIC ET 200SP HA, Terminal block, Type H1, 32 push-in terminals, internal reference temperature New load group, width: 22.5 mm.

Siemens 6DL1193-6TP00-0BH1 SIMATIC ET 200SP HA

Siemens 6DL1193-6TP00-0BH1 SIMATIC ET 200SP HA, Terminal block, Type H1, 32 push-in terminals, internal reference temperature Width: 22.5 mm.

Siemens 6DL1193-6GC00-0NN0 SIMATIC ET 200SP HA

Siemens 6DL1193-6GC00-0NN0 SIMATIC ET 200SP HA, carrier module 8-fold carrier for holding 8 I/O modules of the ET 200SP HA.

Siemens 6DL1193-6GA00-0NN0 SIMATIC ET 200SP HA

Siemens 6DL1193-6GA00-0NN0 SIMATIC ET 200SP HA, carrier module 2-fold carrier for holding 2 I/O modules of the ET 200SP HA.

Assortments

Description

Yokogawa Analog Input Module AAV144-SE3 

  

   STANDARD SPECIFICATIONS of  AAV144-SE3  

   Current/Voltage Input Modules (Non-Isolated)
   These modules provide 16 inputs of mainly 4 to 20 mA DC or 1 to 5 V DC standardized signals from 2-wire/4-wire transmitters.
  They can be used in dual-redundant configuration.

    

     

      Voltage Input Module (Isolated)      

      AAV144  is for 16 inputs of 1 to 5 V or -10 to 10 V signal. It can be used in dual-redundant configuration  

 

ItemsSpecifications
ModelAAV144
Number of output channels16, isolated
Input signal1 to 5 V     10 to 10 V
Switching input signalsInput signals can be set together for CH1 to CH16
Allowable input voltage±30 V
Withstanding isolated voltageBetween input and system: 1500 V AC withstanding voltage, for 1 minute (*1)
Input resistancePower ON   1 MΩ

Power OFF   200 kΩ
Accuracy±4 mV        ±20 mV
Data update period10 ms
Drift due to ambient temperature change±4 mV/10 C              ±20 mV/10 C
Maximum current consumption500 mA (5 V DC)
Weight0.2 kg
External communicationPressure clamp terminal, MIL connector cable, dedicated cable (KS1)

  *1: When the dedicated cable is used, the withstanding voltage is 500 V AC (between the input signal and the system). When
the ML connector cable is used, the withstanding voltage depends on the electrical specifications of the cable.

 

Yokogawa Analog Input Module AAV144-SE3 

 

EXTERNAL DIMENSIONS of  AAV144-SE3 

 

 

  Yokogawa Analog Input Module AAV144-SE3 

 

MODEL AND SUFFIX CODES AAV144-SE3



Description
ModelAAV144Analog Input Module (-10 to +10 V, 16-channel, Isolated)

-SStandard type
Suffix
Codes
   5With no explosion protection

   EWith explosion protection

      0With explosion protection

      3With ISA Standard G3 option and temperature (-20 to 70 °C) option
Option
Codes
/K4A00With KS Cable Interface Adapter [Model: ATK4A-00]

/A4S00With Pressure Clamp Terminal Block for Analog [Model: ATA4S-00]

/A4S10With Pressure Clamp Terminal Block for Analog (surge absorber) [Model: ATA4S-10]

/A4D00With Dual Pressure Clamp Terminal Block for Analog [Model: ATA4D-00]

/A4D10With Dual Pressure Clamp Terminal Block for Analog (surge absorber) [Model: ATA4D-10]

/CCC01With Connector Cover for MIL Cable [Model: ACCC01

 

 

 

Yokogawa Analog Input Module AAV144-SE3