Yokogawa Analog Input Module AAB141-H50
2016-03-21 20:38:04
Description:
Yokogawa Analog Input Module AAB141-H50,Yokogawa Analog I/O modules function as signal converters; by inputting field analog signals into these modules ……
Notice:
Yokogawa Analog Input Module AAB141-H50, Yokogawa original packing, by carton,Place of Origin: Indonesia
New Products
Emerson TREXCHPKL9S1 AMS Trex device communicator
Emerson TREXCHPKL9S1 AMS Trex device communicator. HART Application, ATEX, CSA US/Canada and IECEx intrinsically safe, Standard support 1 year. Enables HART or Fieldbus Module device communications, 5.7 inch touchscreen display, intrinsically safe.
Emerson TREXCHPKLWP3S AMS Trex device communicator
Emerson TREXCHPKLWP3S AMS Trex device communicator. HART Application, ATEX, CSA US/Canada and IECEx intrinsically safe, Wireless, Premium support 3 year, Carrying Case. Enables HART or Fieldbus Module device communications, 5.7 inch touchscreen display, intrinsically safe.
Emerson TREXCHPKLWP3 AMS Trex device communicator
Emerson TREXCHPKLWP3 AMS Trex device communicator. HART Application, ATEX, CSA US/Canada and IECEx intrinsically safe, Wireless, Premium support 3 year. Enables HART or Fieldbus Module device communications, 5.7 inch touchscreen display, intrinsically safe.
Emerson TREXCHPKLWP1S AMS Trex device communicator
Emerson TREXCHPKLWP1S AMS Trex device communicator. HART Application, ATEX, CSA US/Canada and IECEx intrinsically safe, Wireless, Premium support 1 year, Carrying Case. Enables HART or Fieldbus Module device communications, 5.7 inch touchscreen display, intrinsically safe.
Assortments
▶ Pressure Transmitter EJA
▶ Pressure Transmitters EJA-E
▶ Pressue Transmitter EJX
▶ Safety Instrumented System (SIS)
▶ Valve Positioners & Converters
▶ Field Mount Indicators
▶ Temperature Transmitters
▶ Magnetic Flowmeters
▶ Vortex Flowmeter
▶ Ultrasonic Flowmeters
▶ Coriolis Mass Flowmeters - ROTAMASS 3-Series
▶ Variable Area Flowmeters – Rotameters
▶ Device Smart Communicators
▶ PORTABLE AND HANDHELD INSTRUMENTS
▶ Distributed Control System (DCS)
▶ Process Analyzers
▶ Paperless Recorders
▶ Strip Chart Recorders
▶ Data Acquisition Equipment
▶ UT Series Temperature Controllers
▶ UP Series Program Controllers
▶ UM Series Digital Indicators with Alarms
▶ UT100 Series Temperature Controllers
▶ UD Series Manual Setters
▶ Limit Controllers
▶ YS Series Single-loop Controllers
Description
Yokogawa Analog Input Module AAB141-H50
STANDARD SPECIFICATIONS of AAB141-H50
Current/Voltage Input Modules (Non-Isolated)
These modules provide 16 inputs of mainly 4 to 20 mA DC or 1 to 5 V DC standardized signals from 2-wire/4-wire transmitters.
They can be used in dual-redundant configuration.
Items | Specifications | ||||
Model | AAI141 (*1) | AAV141 | AAV142 | AAB141(*1) (*4) | |
Number of input channels | 16, non-isolated | ||||
Input signal | 4 to 20 mA DC | ||||
Allowable input current/voltage | 27 mA | ||||
Withstanding voltage | — | ||||
Input resistance | Power ON | 400 Ω (at 20 mA) to 1000 Ω (at 4 mA) (*2) | 1 MΩ or larger | 1 MΩ or larger | Voltage input : 1 MΩ or larger Current input : 290 Ω (at 20 mA) to 450 Ω (at 4 mA) (*6) |
Power OFF | 500 kΩ or larger | 340 kΩ or larger | 660 kΩ or larger | Voltage input : 340 kΩ or larger Current input : 500 kΩ or larger | |
Accuracy | ±16 μA | ±4 mV | ±20 mV | Voltage input : ±4 mV Current input : ±16 μA | |
Data update period | 10 ms | ||||
Step response time | 100 ms | ||||
Transmitter power supply | 14.8 V or higher (at 20 mA) (*3) 26.4 V or less (at 0 mA) (output current limit: 27 mA) | ||||
Setting of 2-wire or 4-wire transmitter | For each channel by setting pin | ||||
Drift due to ambient temperature change | ±16 μA/10 °C | ±4 mV/10 °C ± | ±20 mV/10 °C | ±0.1 %/10 °C | |
Maximum current consumption | 310 mA (5 V DC), 450 mA (24 V DC) | 350 mA (5 V DC) | 350 mA (5 V DC) | 480 mA (5 V DC), 120 mA (24 V DC) | |
Weight | 0.2 kg | 0.2 kg | 0.2 kg | 0.3 kg | |
External connection | Pressure clamp terminal, KS cable, MIL connector cable | KS cable | |||
External connection | Available | Available (at current input) |
Yokogawa Analog Input Module AAB141-H50
EXTERNAL DIMENSIONS of AAB141-H50
Yokogawa Input Module AAB141-H50
MODEL AND SUFFIX CODES AAB141-H50
Description | ||
Model | AAB141 | Analog Input Module (1 to 5 V/4 to 20 mA, 16-channel, Non-Isolated) |
-H | With digital communication (HART protocol) | |
Suffix Codes | 5 | With no explosion protection |
E | With explosion protection | |
0 | Basic type | |
3 | With ISA Standard G3 option and temperature (-20 to 70 °C) option | |
Ootion codes | /K4A00 | With KS Cable Interface Adapter [Model: ATK4A-00] |