Yokogawa Analog I/O Modules AAI141-H50
2016-03-21 01:01:37
Description:
Yokogawa Analog I/O Modules AAI141-H50,Yokogawa Analog I/O modules function as signal converters; by inputting field analog signals into these modules ……
Yokogawa Analog I/O Modules AAI141-S50,Yokogawa original packing, by carton,Place of Origin: Indonesia
New Products
OMRON CS1W-CN133 CS1 I/O Connecting Cable
OMRON CS1W-CN133 CS1 I/O Connecting Cable. Connects CS1 Expansion I/O Backplanes to CPU Backplanes or other CS1 Expansion I/O Backplanes.
OMRON CS1W-AD041-V1 CS1W series Analog Input Unit
OMRON CS1W-AD041-V1 CS1W series Analog Input Unit. Contact us to learn more about the OMRON CS1G/CS1H/CS1W/CS1D SYSMAC CS1 Programmable Controller.
OMRON CS1H-CPU63H CS1H CPU Unit
OMRON CS1H-CPU63H CS1H CPU Unit. Omron CS1 Series is widely used in industrial automation applications such as production line control, process monitoring, packaging, material handling, and power plant systems.
OMRON CS1G-CPU42H CS1G CPU Unit
OMRON CS1G-CPU42H CS1G CPU Unit. Ideal for control of power generators, water supply utilities, 24/7 production.
Assortments
▶ Pressure Transmitter EJA
▶ Pressure Transmitters EJA-E
▶ Pressue Transmitter EJX
▶ Safety Instrumented System (SIS)
▶ Valve Positioners & Converters
▶ Field Mount Indicators
▶ Temperature Transmitters
▶ Magnetic Flowmeters
▶ Vortex Flowmeter
▶ Ultrasonic Flowmeters
▶ Coriolis Mass Flowmeters - ROTAMASS 3-Series
▶ Variable Area Flowmeters – Rotameters
▶ Device Smart Communicators
▶ PORTABLE AND HANDHELD INSTRUMENTS
▶ Distributed Control System (DCS)
▶ Process Analyzers
▶ Paperless Recorders
▶ Strip Chart Recorders
▶ Data Acquisition Equipment
▶ UT Series Temperature Controllers
▶ UP Series Program Controllers
▶ UM Series Digital Indicators with Alarms
▶ UT100 Series Temperature Controllers
▶ UD Series Manual Setters
▶ Limit Controllers
▶ YS Series Single-loop Controllers
Description
Yokogawa Analog I/O Modules AAI141-H50
STANDARD SPECIFICATIONS of AAI141-H50
Current/Voltage Input Modules (Non-Isolated)
These modules provide 16 inputs of mainly 4 to 20 mA DC or 1 to 5 V DC standardized signals from 2-wire/4-wire
transmitters.
They can be used in dual-redundant configuration.
| Items | Specifications | ||||
| Model | AAI141 (*1) | AAV141 | AAV142 | AAB141(*1) (*4) | |
| Number of input channels | 16, non-isolated | ||||
| Input signal | 4 to 20 mA DC | ||||
| Allowable input current/voltage | 27 mA | ||||
| Withstanding voltage | — | ||||
| Input resistance | Power ON | 400 Ω (at 20 mA) to 1000 Ω (at 4 mA) (*2) | 1 MΩ or larger | 1 MΩ or larger | Voltage input : 1 MΩ or larger Current input : 290 Ω (at 20 mA) to 450 Ω (at 4 mA) (*6) |
| Power OFF | 500 kΩ or larger | 340 kΩ or larger | 660 kΩ or larger | Voltage input : 340 kΩ or larger Current input : 500 kΩ or larger | |
| Accuracy | ±16 μA | ±4 mV | ±20 mV | Voltage input : ±4 mV Current input : ±16 μA | |
| Data update period | 10 ms | ||||
| Step response time | 100 ms | ||||
| Transmitter power supply | 14.8 V or higher (at 20 mA) (*3) 26.4 V or less (at 0 mA) (output current limit: 27 mA) | ||||
| Setting of 2-wire or 4-wire transmitter | For each channel by setting pin | ||||
| Drift due to ambient temperature change | ±16 μA/10 °C | ±4 mV/10 °C ± | ±20 mV/10 °C | ±0.1 %/10 °C | |
| Maximum current consumption | 310 mA (5 V DC), 450 mA (24 V DC) | 350 mA (5 V DC) | 350 mA (5 V DC) | 480 mA (5 V DC), 120 mA (24 V DC) | |
| Weight | 0.2 kg | 0.2 kg | 0.2 kg | 0.3 kg | |
| External connection | Pressure clamp terminal, KS cable, MIL connector cable | KS cable | |||
| External connection | Available | Available (at current input) | |||
Yokogawa Analog I/O Modules AAI141-H50
EXTERNAL DIMENSIONS of AAI141-H50

Yokogawa Analog I/O Modules AAI141-H50
MODEL AND SUFFIX CODES AAI141-H50
| Description | ||
| Model | AAI141 | Analog Input Module (4 to 20 mA, 16-channel, Non-Isolated) |
| -S | Standard type | |
| -H | With digital communication (HART protocol) | |
| Suffix Codes | 5 | With no explosion protection |
| E | With explosion protection | |
| 0 | Basic type | |
| 3 | With ISA Standard G3 option and temperature (-20 to 70 °C) option | |
| /K4A00 | With KS Cable Interface Adapter [Model: ATK4A-00] | |
| /A4S00 | With Pressure Clamp Terminal Block for Analog [Model: ATA4S-00] | |
| /A4S10 | With Pressure Clamp Terminal Block for Analog (surge absorber) [Model: ATA4S-10] | |
| Option Codes | /A4D00 | With Dual Pressure Clamp Terminal Block for Analog [Model: ATA4D-00] |
| /A4D10 | With Dual Pressure Clamp Terminal Block for Analog (surge absorber) [Model: ATA4D-10] | |
| /CCC01 | With Connector Cover for MIL Cable [Model: ACCC01] |