Yokogawa TC/mV Input Module AAT145-S50
2016-03-21 00:02:27
Description:
Yokogawa TC/mV Input Module AAT145-S50, okogawa Analog I/O modules function as signal converters; by inputting field analog signals into these modules ……
Yokogawa original packing, by carton, Place of Origin: Indonesia
New Products
Orbinox VG SERIES 61 Slurry knife gate valve
Orbinox SERIES 61 (VG) model knife gate valve is a wafer type valve equipped with two metal reinforced rubber sleeves,designed for applications with abrasive slurries.
Crosby J-Series Direct Spring Pressure Relief Valves
J-Series valves provide high quality and dependable overpressure protection for air, gas, steam, vapor, liquid and two-phase applications in one simple design. Now available with two new to the world technologies, Balanced Diaphragm and Bellows Leak Detection.
Vanessa Series 30,000 Cryogenic Triple Offset Valve
The Vanessa Series 30,000 Cryogenic Triple Offset Valve is a virtually maintenance-free valve with tightness, operability and torque demand unaffected by cryogenic conditions and severe temperature fluctuations.
Sempell Model SOT High pressure steam safety valve
The Sempell Model SOT is a high-pressure steam safety valve designed for boiler protection and steam system safety.
Assortments
▶ Pressure Transmitter EJA
▶ Pressure Transmitters EJA-E
▶ Pressue Transmitter EJX
▶ Safety Instrumented System (SIS)
▶ Valve Positioners & Converters
▶ Field Mount Indicators
▶ Temperature Transmitters
▶ Magnetic Flowmeters
▶ Vortex Flowmeter
▶ Ultrasonic Flowmeters
▶ Coriolis Mass Flowmeters - ROTAMASS 3-Series
▶ Variable Area Flowmeters – Rotameters
▶ Device Smart Communicators
▶ PORTABLE AND HANDHELD INSTRUMENTS
▶ Distributed Control System (DCS)
▶ Process Analyzers
▶ Paperless Recorders
▶ Strip Chart Recorders
▶ Data Acquisition Equipment
▶ UT Series Temperature Controllers
▶ UP Series Program Controllers
▶ UM Series Digital Indicators with Alarms
▶ UT100 Series Temperature Controllers
▶ UD Series Manual Setters
▶ Limit Controllers
▶ YS Series Single-loop Controllers
Description
Yokogawa TC/mV Input Module AAT145-S50
STANDARD SPECIFICATIONS of AAT145-S50
TC/RTD Input Modules (Isolated Channels)
AAT145, AAR145 These modules receive signals from mV, thermocouple (TC), RTD, and potentiometer (POT), and they are isolated between the field and the system as well as in between each channel. They can be used in dual-redundant configuration.
Items | Specifications | |
Model | AAT145 | AAR145 |
Number of input channels | 16, isolated channels | 16, isolated channels |
Input signal | TC: JIS C1602:1995 (*1), IEC584:1995 Type J, K, E, B (*2), R, S, T, N mV: -100 to 150 mV, -20 to 80 Mv | RTD: JIS C1604:1997 (*3), IEC751:1995 Pt100 (3-wire type) POT: Total resistance 100 Ω to 10 kΩ Span resistance: 50 % or larger of total resistance |
Switching input signals | TC/mV can be set individually for CH1 to CH16 | RTD/POT can be selected individually for CH1 to CH16. |
Allowable input voltage | ±5 V | ±5 V |
Withstanding voltage | Between input and system: 500 V AC (for single card: 1500 V AC), For 1 minute Between input channels: 200 V AC, For 1 minute | |
Input resistance | Power ON 1 MΩ or larger | |
Power OFF 1 MΩ or larger | ||
Accuracy | ±40 μV | RTD: ±150 mΩ POT: ±0.2 %/FS |
Allowable total resistance of signal source plus wiring | 1000 Ω or less | 150 Ω or less (wiring resistance per wire) (*4) |
Effect of allowable signal source resistance (1000 Ω) | ±20 μV | |
Reference junction compensation accuracy | ±1 °C (*5) (6) | |
Measurement current | RTD: 1 mA | |
Data update period | 1 s | |
Burn-out | All channels can be set together. Setting: not available/available (UP/DOWN) Detection time: 60 s | |
Temperature drift | ±80 μV/10 °C | RTD: ±0.3 Ω/10 °C POT: ±0.4 %/10 °C |
Maximum current consumption | 350 mA (5 V DC) | 350 mA (5 V DC) |
Weight | 0.3 kg | |
External connection | Dedicated cable (KS1) | Dedicated cable (KS8/AKB335) |
Yokogawa TC/mV Input Module AAT145-S50
EXTERNAL DIMENSIONS of AAT145-S50
Yokogawa TC/mV Input Module AAT145-S50
MODEL AND SUFFIX CODES AAT145-S50
Description | ||
Model | AAT145 | TC/mV Input Module (16-channel, Isolated channels) |
Suffix Codes | -S | Standard type |
5 | With no explosion protection | |
E | With explosion protection | |
0 | Basic type | |
3 | With ISA Standard G3 option and temperature (-20 to 70 °C) option |
Yokogawa TC/mV Input Module AAT145-S50