Eaton MTL4521/L-MTL5521 MTL Intrinsically Safety Intrinsically Safe Isolators MTL 5500 range solenoid driver
2018-06-22 09:43:08
Description:
The MTLx521 and the MTL4521L are loop-powered modules which enable a device located in the hazardous area to be controlled from the safe area. They can all drive a certified intrinsically safe low-power load, as well as non-energy-storing simple apparatus such as an LED.……
New Products
Siemens 6DL1193-6TP00-0DH1 SIMATIC ET 200SP HA
Siemens 6DL1193-6TP00-0DH1 SIMATIC ET 200SP HA, Terminal block, Type H1, 32 push-in terminals, internal reference temperature New load group, width: 22.5 mm.
Siemens 6DL1193-6TP00-0BH1 SIMATIC ET 200SP HA
Siemens 6DL1193-6TP00-0BH1 SIMATIC ET 200SP HA, Terminal block, Type H1, 32 push-in terminals, internal reference temperature Width: 22.5 mm.
Siemens 6DL1193-6GC00-0NN0 SIMATIC ET 200SP HA
Siemens 6DL1193-6GC00-0NN0 SIMATIC ET 200SP HA, carrier module 8-fold carrier for holding 8 I/O modules of the ET 200SP HA.
Siemens 6DL1193-6GA00-0NN0 SIMATIC ET 200SP HA
Siemens 6DL1193-6GA00-0NN0 SIMATIC ET 200SP HA, carrier module 2-fold carrier for holding 2 I/O modules of the ET 200SP HA.
Assortments
Description
Eaton MTL4521/L-MTL5521 MTL Intrinsically Safety Intrinsically Safe Isolators MTL 5500 range
Loop powered solenoid driver, IIC
Solenoid/ Alarm Driver loop-powered, IIC
Similar Types : MTL5018AC, MTL5501-SR, MTL5510, MTL5510B, MTL5511, MTL5513, MTL5514, MTL5514D, MTL5516C, MTL5517, MTL5521, MTL5522, MTL5523, MTL5523V-VL, MTL5524, MTL5525, MTL5526, MTL5541, MTL5541A, MTL5541AS, MTL5541S, MTL5544, MTL5544A, MTL5544AS, MTL5544D, MTL5544S, MTL5546, MTL5546Y, MTL5549, MTL5549Y, MTL5573, MTL5575, MTL5576-RTD, MTL5576-THC, MTL5581, MTL5582, MTL5582B, MTL5531, MTL5532, MTL5561, MPA5500, MTL5051, MTL5053, MTL5314, MTL5599, PSG60E24RM (replaces MTL5991)
The MTLx521 and the MTL4521L are loop-powered modules which enable a device located in the hazardous area to be controlled from the safe area. They can all drive a certified intrinsically safe low-power load, as well as non-energy-storing simple apparatus such as an LED.
Number of channels
One
Location of load
Zone 0, IIC, T4–6 hazardous area if suitably certified
Div. 1, Group A hazardous location
Input voltage
20 to 35V dc
Hazardous-area output (MTLx521)
Minimum output voltage: 13.6V at 48mA
Maximum output voltage: 24V from 180
Current limit: 48mA minimum
Hazardous-area output (MTL4521L)
Minimum output voltage: 11.1V at 48mA
Maximum output voltage: 24V from 232
Current limit: 48mA minimum
Output ripple
< 0.5% of maximum output, peak to peak
Response time
Output within 10% of final value within 100ms
LED indicator
Yellow: output status, on when output active
Maximum current consumption
90mA at 24V
Power dissipation within unit
1.4W at 24V
Safety description (MTLx521)
Uo=25V Io=147mA Po=0.92W Um = 253V rms or dc
Safety description (MTL4521L)
Uo= 25V Io= 108mA Po= 0.68W Um = 253V rms or dc
If you have any question, please do not hesitate to contact with me online
Contact details :
Shirley Sun
Sales Engineer
HONGKONG XIEYUAN TECH CO., LIMITED
Add : 7-A16, Caishen Commercial Plaza, Hangkou Railway Station, Wuhan, China
M : +86-15172506760 (WhatsApp & Wechat) | T : +86-27-85309780 | F : +86-27-85309780
Email : Shirley@whxyauto.com Skype : 169649423@qq.com
Web : www.hkxytech.com