  • Models 112.28, 132.28 Bourdon tube pressure gauge Industrial series

Models 112.28, 132.28 Bourdon tube pressure gauge Industrial series

2015-06-17 21:10:57

Description:

Models 112.28, 132.28 Bourdon tube pressure gauge Industrial series……

New Products

OMRON 3G3MX2-AB022-V2 inverter drive

OMRON 3G3MX2-AB022-V2 MX2-EV2 inverter drive, 2.2/3.0 kW (ND/LD), 11.0/12.0 A (ND/LD), 200 VAC, 1~ input, sensorless vector, max. output freq. 590Hz

OMRON 3G3MX2-AB015-V2 inverter drive

OMRON 3G3MX2-AB015-V2 MX2-EV2 inverter drive, 1.5/2.2 kW (ND/LD), 8.0/9.6 A (ND/LD), 200 VAC, 1~ input, sensorless vector, max. output freq. 590Hz.

OMRON 3G3MX2-AB007-V2 inverter drive

OMRON 3G3MX2-AB007-V2 MX2-EV2 inverter drive, 0.75/1.1 kW (ND/LD), 5.0/6.0 A (ND/LD), 200 VAC, 1~ input, sensorless vector, max. output freq. 590Hz

OMRON 3G3MX2-AB004-V2 inverter drive

OMRON 3G3MX2-AB004-V2 MX2-EV2 inverter drive, 0.4/0.55 kW (ND/LD), 3.0/3.5 A (ND/LD), 200 VAC, 1~ input, sensorless vector, max. output freq. 590Hz

Assortments

Description

 

Applications

  • For gaseous and liquid media that are not highly viscous or crystallising

  • Model 112.28: Measuring system Cu-alloy
    Model 132.28: Measuring system stainless steel, also for aggressive media

  • Hydraulics

  • Compressors

  • Refrigeration technology


Special features

  • Vibration and shock resistant

  • Especially sturdy design

  • Stainless steel case

  • Scale ranges up to 0 … 40 bar


Description

Design
EN 837-1

Nominal size in mm
80

Accuracy class
1.6

Scale ranges
Model 112.28: 0 ... 0.6 to 0 ... 40 bar
Model 132.28: 0 ... 1 to 0 ... 40 bar
or all other equivalent vacuum or combined pressure and vacuum ranges

Pressure limitation
Steady: Full scale value
Fluctuating: 0.9 x full scale value
Short time: 1.3 x full scale value

Permissible temperature
Ambient: 

-40 ... +60 °C
Medium: 
+60 °C maximum (model 112.28)
+200 °C maximum (model 132.28)

Temperature effect
When the temperature of the measuring system deviates
from the reference temperature (+20 °C):
Max. ±0.4 %/10 K of full scale value

Ingress protection
IP 54 per EN 60529 / lEC 529