Top Industrial Automation and Electrical Instrument from HKXYTECH
  • YOKOGAWA ESD SAT145 TC/mV Input Module

YOKOGAWA ESD SAT145 TC/mV Input Module

2016-06-15 00:14:23

Description:

SAI143 SAV144 SAI533 SAT145 SDV144 SDV531 SDV541 SDV521 SDV526 Our Products covers ESD (Emergency Shut Down), F&G or FGS (Fire and Gas Systems), BMS (Burner or Boiler Management Systems) as well as HIPPS or HIPS (High Integrity (Pipeline) Protection Systems)..……

Notice:
I/O Module Place of Origin: Japan,Yokogawa original packing, by carton

New Products

Emerson TREXCHPKL9S1 AMS Trex device communicator

Emerson TREXCHPKL9S1 AMS Trex device communicator. HART Application, ATEX, CSA US/Canada and IECEx intrinsically safe, Standard support 1 year. Enables HART or Fieldbus Module device communications, 5.7 inch touchscreen display, intrinsically safe.

Emerson TREXCHPKLWP3S AMS Trex device communicator

Emerson TREXCHPKLWP3S AMS Trex device communicator. HART Application, ATEX, CSA US/Canada and IECEx intrinsically safe, Wireless, Premium support 3 year, Carrying Case. Enables HART or Fieldbus Module device communications, 5.7 inch touchscreen display, intrinsically safe.

Emerson TREXCHPKLWP3 AMS Trex device communicator

Emerson TREXCHPKLWP3 AMS Trex device communicator. HART Application, ATEX, CSA US/Canada and IECEx intrinsically safe, Wireless, Premium support 3 year. Enables HART or Fieldbus Module device communications, 5.7 inch touchscreen display, intrinsically safe.

Emerson TREXCHPKLWP1S AMS Trex device communicator

Emerson TREXCHPKLWP1S AMS Trex device communicator. HART Application, ATEX, CSA US/Canada and IECEx intrinsically safe, Wireless, Premium support 1 year, Carrying Case. Enables HART or Fieldbus Module device communications, 5.7 inch touchscreen display, intrinsically safe.

Assortments

Description

YOKOGAWA ESD Analog Input Module SAI144 Series

 

STANDARD SPECICATIONS

 

 

TC/mV Input Module

 

This module receives signals from mV and thermocouple (TC). The SAT145 can be made dual redundant.


Item




Specifications


Model


SAT145





Number of input channels

16-channel, Isolated Channels




TC: JIS C 1602, IEC 60584-1 (ITS-90)




J: -210 to 1200 °C

K: -270 to 1372 °C




E: -270 to 1000 °C

T: -270 to 400 °C


Input signal

S: -50 to 1767 °C

R: -50 to 1767 °C




N: -270 to 1300 °C

B: 42 to 1820 °C




mV







-100 to 150 mV, -20 to 80 mV, -5 to 25 mV





Switching input signals

TC/mV can be set individually for CH1 to CH16.


Permissible input range

± 5 V





Withstand voltage (*1)

Between input and system: 1500 V AC for 1 minute


Between channels: 200 V AC for 1 minute









Input impedance

At least 1 MΩ during Power-ON


At least 1 MΩ during Power-OFF











Accuracy

TC

± 40 μV



mV

± 40 μV













Allowable total resistance of signal

1000 Ω or less



source plus wiring








Effect of allowable signal source

± 20 μV (*2)




resistance (1000 Ω)









Reference junction compensation

-20 to 0 °C

± 1.5 °C



0 to 30 °C


± 1.0 °C



accuracy (*3) (*4)




30 to 70 °C

± 1.5 °C











Temperature drift

± 40 μV / 10 °C



Data update period

150 ms





Burn-out


Individual channel setting



Setting: Burnout upscale/Burnout downscale




Detection time: 1.5 s








Ambient temperature (during operation)

-20 to 70 °C




Maximum current consumption

5 V system: 400 mA



24 V system: 200 mA












Weight


Approx. 0.47 kg



External connection

Dedicated signal cable (AKB331)


 

YOKOGAWA ESD Analog Input Module SAT145

 

 MODEL AND SUFFIX CODES

 



Description

Model

SAT145

TC/mV Input Module (16-channel, Isolated Channels)

 

 

Suffix Codes

-S

Standard type

     6

With signal cable interface adapter and no explosion protection

     F

With signal cable interface adapter and explosion protection

        3

With ISA Standard G3 and temperature (-20 to 70 ºC)

Option Codes

/PRP

With prevention pin of false insertion

 

 

ORDERING INFORMATION

Specify the model and suffix codes.

For selecting the right products for explosion protection, please refer to TI 32S01J30-01E without fail.

 

 

SAT145 TC/mV Input Module (16-channel, Isolated Channels)

SAT145-S63 ,SAT145-S63/PRP, SAT145-SF3/PRP

 

YOKOGAWA ESD Analog Input Module SAT145