YOKOGAWA ESD Analog Input Module SAI143-S53/PRP
2016-06-13 23:18:23
Description:
YOKOGAWA ESD SAI143-S53 This GS describes the hardware specifications of the analog I/O modules that can be mounted on the safety node unit and the safety control unit.……
Notice:
YOKOGAWA ESD SAI143-S53 Place of Origin: Singapore,Yokogawa original packing, by carton
New Products
Emerson TREXCHPKL9S1 AMS Trex device communicator
Emerson TREXCHPKL9S1 AMS Trex device communicator. HART Application, ATEX, CSA US/Canada and IECEx intrinsically safe, Standard support 1 year. Enables HART or Fieldbus Module device communications, 5.7 inch touchscreen display, intrinsically safe.
Emerson TREXCHPKLWP3S AMS Trex device communicator
Emerson TREXCHPKLWP3S AMS Trex device communicator. HART Application, ATEX, CSA US/Canada and IECEx intrinsically safe, Wireless, Premium support 3 year, Carrying Case. Enables HART or Fieldbus Module device communications, 5.7 inch touchscreen display, intrinsically safe.
Emerson TREXCHPKLWP3 AMS Trex device communicator
Emerson TREXCHPKLWP3 AMS Trex device communicator. HART Application, ATEX, CSA US/Canada and IECEx intrinsically safe, Wireless, Premium support 3 year. Enables HART or Fieldbus Module device communications, 5.7 inch touchscreen display, intrinsically safe.
Emerson TREXCHPKLWP1S AMS Trex device communicator
Emerson TREXCHPKLWP1S AMS Trex device communicator. HART Application, ATEX, CSA US/Canada and IECEx intrinsically safe, Wireless, Premium support 1 year, Carrying Case. Enables HART or Fieldbus Module device communications, 5.7 inch touchscreen display, intrinsically safe.
Assortments
▶ Pressure Transmitter EJA
▶ Pressure Transmitters EJA-E
▶ Pressue Transmitter EJX
▶ Safety Instrumented System (SIS)
▶ Valve Positioners & Converters
▶ Field Mount Indicators
▶ Temperature Transmitters
▶ Magnetic Flowmeters
▶ Vortex Flowmeter
▶ Ultrasonic Flowmeters
▶ Coriolis Mass Flowmeters - ROTAMASS 3-Series
▶ Variable Area Flowmeters – Rotameters
▶ Device Smart Communicators
▶ PORTABLE AND HANDHELD INSTRUMENTS
▶ Distributed Control System (DCS)
▶ Process Analyzers
▶ Paperless Recorders
▶ Strip Chart Recorders
▶ Data Acquisition Equipment
▶ UT Series Temperature Controllers
▶ UP Series Program Controllers
▶ UM Series Digital Indicators with Alarms
▶ UT100 Series Temperature Controllers
▶ UD Series Manual Setters
▶ Limit Controllers
▶ YS Series Single-loop Controllers
Description
YOKOGAWA ESD Analog Input Module SAI143-S53
n STANDARD SPECIFICATIONS
l Current Input Module
This module inputs 4 to 20 mA signals from the field.
The SAI143 can be made dual redundant.
Item | Specifications | ||
Model | SAI143 (*1) | ||
Number of input channels | 16-channel, module isolation (*5) | ||
Rated input range | 4 to 20 mA | ||
Permissible input range | 0 to 25 mA | ||
Input impedance during Power-ON | 250 Ω+ Voltage drop in the input protection circuit inside the module | (*6) | |
Current value | |||
Input impedance during Power-OFF | 500 kΩ minimum | ||
Rated accuracy | SAI143-S : ±16 µA (Input range 1 to 23 mA) | ||
SAI143-H : ±16 µA (Input range 0.05 to 23 mA) (*3) (*4) | |||
Data update frequency | 40 ms | ||
Temperature drift | ±16 µA/10 °C | ||
Transmitter power supply | 16.15 V minimum (at 20 mA) | ||
26.4 V maximum (at 0 mA) | |||
(Output current limit: 25 mA) | |||
2/4-wire setting | Individual channel setting | ||
Changed by setting pins | |||
Withstand voltage | 1.5 kV AC between input signal and system for 1 minute (*2) | ||
Maximum current consumption | 5 V system: 320 mA, | ||
24 V system: 550 mA | |||
Weight | Approx. 0.34 kg (For pressure clamp terminal block or MIL cable) | ||
Approx. 0.39 kg (With signal cable interface adapter) | |||
External connection | Pressure clamp terminal | ||
MIL cable | |||
Dedicated signal cable | |||
Support PRM | Available (SAI143-H) |
YOKOGAWA ESD Analog Input Module SAI143-S53
n MODEL AND SUFFIX CODES
Description | ||
Model | SAI143 | Analog Input Module (4 to 20 mA, 16-channel, module isolation) |
Suffix Codes | -S | Standard type |
-H | With HART communication [Release: R1.02.00] (*1) | |
5 | For pressure clamp terminal block or MIL cable with no explosion protection | |
6 | With signal cable interface adapter and no explosion protection (*2) | |
E | For pressure clamp terminal block or MIL cable with explosion protection | |
F | With signal cable interface adapter and explosion protection (*2) | |
3 | With ISA Standard G3 and temperature (-20 to 70 ºC) | |
C | With ISA Standard G3 and high-density installation (-20 to 70 ºC) (*5) | |
Option Codes |
/A4S00 | With pressure clamp terminal block for analog [Model: STA4S-00] |
/A4S10 | With pressure clamp terminal block for analog (with surge absorber) [Model: STA4S-10] | |
/A4D00 | With dual-redundant pressure clamp terminal block for analog (*3) [Model: STA4D-00] | |
/A4D10 | With dual-redundant pressure clamp terminal block for analog (with surge absorber) (*3) [Part name: STA4D-10] | |
/PRP | With prevention pin of false insertion (*4) | |
/CCC01 | With connector cover for MIL cable (for flat ribbon cable) [Model: SCCC01] |
n ORDERING INFORMATION
Specify the model and suffix codes.
For selecting the right products for explosion protection, please refer to TI 32S01J30-01E without fail.
SAI143 Analog Input Module (4 to 20 mA, 16-channel, module isolation)
SAI143-S53/A4S00 , SAI143-S53/A4S10 , SAI143-S53/A4D00 , SAI143-S53/A4D10 ,SAI143-S53/PRP, SAI143-S53/CCC01
SAI143-S63/A4S00 , SAI143-S63/A4S10 , SAI143-S63/A4D00 , SAI143-S63/A4D10 ,SAI143-S63/PRP, SAI143-S63/CCC01
SAI143-SE3/A4S00 , SAI143-SE3/A4S10 , SAI143-SE3/A4D00 , SAI143-SE3/A4D10 ,SAI143-SE3/PRP, SAI143-SE3/CCC01
SAI143-SF3/A4S00 , SAI143-SF3/A4S10 , SAI143-SF3/A4D00 , SAI143-SF3/A4D10 ,SAI143-SF3/PRP, SAI143-SF3/CCC01
SAI143-S5C/A4S00 , SAI143-S5C/A4S10 , SAI143-S5C/A4D00 , SAI143-S5C/A4D10 ,SAI143-S5C/PRP, SAI143-S5C/CCC01
SAI143-S6C/A4S00 , SAI143-S6C/A4S10 , SAI143-S6C/A4D00 , SAI143-S6C/A4D10 ,SAI143-S6C/PRP, SAI143-S6C/CCC01
SAI143-SEC/A4S00 , SAI143-SEC/A4S10 , SAI143-SEC/A4D00 , SAI143-SEC/A4D10 ,SAI143-SEC/PRP, SAI143-SEC/CCC01
SAI143-SFC/A4S00 , SAI143-SFC/A4S10 , SAI143-SFC/A4D00 , SAI143-SFC/A4D10 ,SAI143-SFC/PRP, SAI143-SFC/CCC01